40 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
Figure 24. Floor Stand Attachment Hardware
55..22 PPoowweerr CCoonnnneeccttiioonnss
All wiring must comply with NEC and local codes.
Installers are responsible for selecting appropriate wiring.
55..22..11 UUppssttrreeaamm CCiirrccuuiitt BBrreeaakkeerr PPrrootteeccttiioonn
Customers must provide upstream circuit breaker protection for the input wires to the TFA STS as required by
the National Electric Code (NEC). For additional information, refer to your local codes and the NEC.
55..22..22 PPoowweerr SSoouurrcceess
The two input feeds for the TFA STS should be from separate and independent sources to avoid a common
source failure. The input feeds should nominally be of the same voltage and phase rotation. The input power
wire size should be based on the upstream over current protection device, conforming to NEC and local codes.
Installation TFA STS 800-1200A Models