SPECIFICATIONS
Eaton
®
9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com
84
Table 19. Electrical Output (All Models)
All Models Normal Mode Battery Mode
Voltage Regulation ±2% Nominal output voltage ±3%
Efficiency >95% (High Efficiency mode), >88% >79.5% (700 VA),
>82% (1000–1500 VA),
>84% (2000–3000 VA)
Frequency Regulation Sync with line ±3 Hz of nominal line
frequency (outside this range:
±0.1 Hz of auto-selected nominal
frequency)
±0.1 Hz of auto-selected nominal
frequency
Low Voltage Models High Voltage Models
Nominal Outputs 100/110/120/127V
(voltage configurable or
auto-sensing)
1000/1500/2000/3000 VA
0.9/1.35/1.8/2.7 kW
200/208/220/230/240V
(voltage configurable or
auto-sensing)
1000/1500/2000/3000 VA
0.9/1.35/1.8/2.7 kW
Frequency 50 or 60 Hz, autosensing or configurable as a frequency converter
Output Overload (Normal Mode) 100–102%: Activates Overload alarm. (Level 1)
102–129%: Load transfers to Bypass mode after 12 seconds. (Level 2)
130–149%: Load transfers to Bypass mode after 2 seconds. (Level 3)
>
150%: Load transfers to Bypass mode after 100 ms. (Level 4)
NOTE Default configuration transfers immediately to Bypass at >102%.
Output Overload (Bypass Mode) 100–109%: Activates Overload alarm. (Level 1)
110–129%: UPS shuts down after 5 minutes. (Level 2)
130–149%: UPS shuts down after 15 seconds. (Level 3)
>
150%: UPS shuts down after 300 ms. (Level 4)
Output Overload (Battery Mode) 100–102%: Activates Overload alarm. (Level 1)
102–129%: UPS shuts down after 12 seconds. (Level 2)
130–149%: UPS shuts down after 2 seconds. (Level 3)
>
150%: UPS shuts down after 100 ms. (Level 4)
Voltage Waveform Sine wave
Harmonic Distortion <3% THD on linear load; <5% THD on non-linear load
Transfer Time Online mode: 0 ms (no break)
High Efficiency mode: 5 ms maximum (due to loss of utility)
Power Factor 0.9
Load Crest Factor 3 to 1