SPECIFICATIONS
Eaton
®
9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com
90
Table 25. Battery
Internal Batteries EBMs
Rackmount
Configuration
700–1000 VA models: 36 Vdc (3 12V, 9 Ah)
1500 VA models: 48 Vdc (4 12V, 9 Ah)
2000–3000 VA models: 72 Vdc (6 12V, 9 Ah)
PW9130N1000R-EBM2U: 36 Vdc (2x3 12V, 9 Ah)
PW9130N1500R-EBM2U: 48 Vdc (2x4 12V, 9 Ah)
PW9130N3000R-EBM2U: 72 Vdc (2x6 12V, 9 Ah)
Tower
Configuration
700 VA models: 24 Vdc (2 12V, 9 Ah)
1000 VA models: 36 Vdc (3 12V, 9 Ah)
1500 VA models: 48 Vdc (4 12V, 9 Ah)
2000–3000 VA models: 96 Vdc (8 12V, 9 Ah)
PW9130N1000T-EBM: 36 Vdc (2x3 12V, 9 Ah)
PW9130N1500T-EBM: 48 Vdc (2x4 12V, 9 Ah)
PW9130N3000T-EBM: 96 Vdc (2x8 12V, 9 Ah)
Fuses Not applicable (4) 30A/125 Vdc fuses per EBM
Type Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F)
Monitoring Advanced monitoring for earlier failure detection and warning
Recharge Time
(to 90%)
Internal batteries: 3 hours
1 EBM: 9 hours; 2 EBMs: 15 hours; 3 EBMs: 21 hours; 4 EBMs: 27 hours
Battery Port External three-pole Anderson connector on UPS for connection to EBM

Table of Contents