Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications
18
P16 Technical Specifications*
Electrical Input
Nominal Voltage 230 Vac
Input Voltage Ranges 150–288V (without using batteries)
Input Power Factor >0.95 typical
Frequency 50/60 Hz, auto-sensing
Frequency Range 46–65 Hz
Electrical Output
On Utility Voltage Regulation ±3% of nominal
On Battery Voltage Regulation ±3% of nominal
Efficiency 89–92% depending on load
Frequency Regulation ±3 Hz online; ±1 Hz on battery
Load Crest Factor 3 to 1 ratio
Communications
Communication Port Relay port standard; optional X-Slot cards available
Communication Cable 6-ft AS/400 communication cable included
Battery
UPS Internal Battery Type 9 Ah, sealed, maintenance-free lead-acid
UPS Internal Battery Type 9 Ah, sealed, maintenance-free lead-acid
Battery Runtime See Battery Runtime Chart
Battery Replacement Hot-swappable UPS internal batteries and external batteries modules
Recharge Time <2 hours from complete discharge to 80% capacity at nominal line conditions
Start-On-Battery Allows start of UPS without utility input
General
Topology True online, double-conversion
Diagnostics Full system self-test on power up
UPS Bypass Automatic on overload or UPS failure
Dimensions and Weight See Model Guide
Environmental and Safety
Ambient Operating Temperature 0°C to 40°C (32°F to 104°F) 0°C to 25°C (32°F to 77°F)
Heat Dissipation 645 BTU/hr maximum
Leakage Current <0.6 mA typical
Storage Temperature 0°C to 25°C (32°F to 77°F)
Relative Humidity 0% to 90% noncondensing
Audible Noise <45 dBA typical
Safety Markings CSA, VDE, CE, S, D, N, FI, B NOM, R
EMC Compliance FCC Class B and VCCI Class II, 3000 FCC Class A
Surge Suppression IEEE/ANSI C62.41 Category B (formerly 587)
REPO Port Meets NEC code 645-11 intent and UL requirements
Network Transient Protector In and out jack for models only or 10BaseT network cable protection. UL497A tested
* Due to continuing product improvement programs, specifications subject to change without notice.