10 Error Messages
10.3 Error list
166 DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
09
V-t
Excessively low
temperature (frost)
Excessively low heat sink temperature • The variable frequency drive will be switched
off if the ambient air temperature is lower than
-10 °C.
• Raise the temperature over -10 °C in order to
start the variable frequency drive.
0A
P-dEF
Parameter Default The parameter's default setting has
been loaded.
Press the STOP pushbutton.
The DC1 variable frequency drive is ready for an
application-specific configuration.
0B
E-triP
External fault • External shutdown (on digital input
3)
• PTC overtemperature (motor)
• External safety shutdown at digital input 3. The
N/C contact has opened due to some reason.
• If a motor thermistor is connected, check
whether the motor is too hot.
0C
SC-trF
Communication fault Communication loss error • Check the communications connection between
the variable frequency drive and the external
devices.
• Make sure that each individual variable
frequency drive on the network has a unique
address.
0E
P-LoSS
Mains connection
phase fault
Input phase loss
Shutdown
• A variable frequency drive intended for use with
a three-phase power supply has lost one of its
input phases.
0F
SPIn-F
Motor pick-up control
fault
Motor pick-up control function (for
catching spinning motors) failed
• The motor pick-up control function did not deter-
mine the motor speed.
10
th-Frt
Thermistor fault Defective thermistor on heat sink • Please contact your closest Eaton representa-
tive.
11
dAtA-F
Data error Internal memory error • Parameter not stored; restore default settings.
• If the problem occurs again, please contact your
closest Eaton representative.
12
4-2OF
Live zero error Analog input current outside range • Make sure that the input current falls within the
range defined in parameter P-16.