Instruction Leaflet IL040029EN
Effective December 2017
18 EATON www.eaton.com
PowerXL DH1 Series VFD
North America cable and fuse sizes—525 Vac to 600 Vac ratings
Notes
Line and motor cable size is selected according to UL 508C Table 40.3 for copper conductor rated 75 °C. Use only with copper wire rated 75 °C here.
Size requirements for other different wire types are defined in the National Electrical Code, ANSI/NFPA 70.
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 508C Table 6.4.
If power cubes or bypass are used, a UL listed Class RK5, J, T or equivalent fuse is recommended.
Frame size Amp suffix
575 V input
current (VT/I
L
)
NEC motor amp
rating at 575 V
Current (VT/I
L
)
at 40 °C
Recommended
fuse rating
NEC wire
Size (AWG) Terminal connection size (AWG)
Line and
motor Ground Line and motor Ground
FR1 4D5 4.2 3.9 4.5 10 14 14 26–10 18–10
7D5 7 6.1 7.5 10 14 12 26–10 18–10
010 9.3 9 10 15 14 10 26–10 18–10
FR2 013 12.5 11 13.5 20 12 10 20–6 12–6
018 16.7 17 18 30 10 10 20–6 12–6
022 20.4 22 22 35 10 8 20–6 12–6
FR3 027 25.2 27 27 40 6 8 6–2 14–4
034 31.7 32 34 45 6 8 6–2 14–4
041 38.2 41 41 50 6 6 6–2 14–4
FR4 052 48.1 52 52 70 4 6 6–1/0 10–1/0
062 57.4 62 62 80 4 6 6–1/0 10–1/0
080 73 77 80 125 2 4 6–1/0 10–1/0
FR5 100 91.3 99 100 150 1/0 4 1/0–350 kcmil 8–250 kcmil
125 114.1 125 125 175 2/0 4 1/0–350 kcmil 8–250 kcmil
144 132.9 144 144 200 3/0 4 1/0–350 kcmil 8–250 kcmil
FR6 208 202.8 192 208 400 2*1/0 3 2*(1/0–300 kcmil) 3–300 kcmil
250 243.8 242 250 400 2*2/0 3 2*(1/0–300 kcmil) 3–300 kcmil