Instruction Leaflet IL040029EN
Effective December 2017
PowerXL DH1 Series VFD
EATON www.eaton.com 17
International cable and fuse sizes—380 Vac to 440 Vac ratings
Notes
Line and motor cable size is selected according to IEC 60364-5-52:2009 Table B.52.4 for copper conductor with PVC insulation with a wiring condition of ambient temperature 30 °C in air and an installation
method of “B2” (cables in conduit and cable trunking systems). For other wiring conditions, please refer to the standard of IEC 60364-5-52:2009 for suitable cable sizes.
Earthing conductor size is determined by the cross-sectional area of phase conductors according to IEC/EN 61800-5-1:2007 Table 5. So if phase conductor size is changed, earthing conductor size should also be
changed accordingly.
If power cubes or bypass are used, a Class gG/gL fuse is recommended.
FR0 is not available till June 2018.
Frame size
Amp
suffix
400 V input
current
(VT/I
L
)
Current
(VT/I
L
)
at 40 °C
Fuse
rating
(gG/gL)
Mains and motor
cable Cu (mm
2
)
Terminal cable size
Main terminal
Cu (mm
2
)
Earth terminal
Cu (mm
2
)
FR0
3D3 4.3 3.3 6 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
4D3 5.5 4.3 10 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
5D6 7.1 5.6 10 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
7D6 9.6 7.6 16 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
FR1 3D3 3.1 3.3 6 3*1.5+1.5 0.2–6 solid or
0.2–4 stranded
0.75–6
4D3 4 4.3 6 3*1.5+1.5 0.75–6
5D6 5.2 5.6 10 3*1.5+1.5 0.75–6
7D6 7.1 7.6 16 3*1.5+1.5 0.75–6
9D0 8.4 9 16 3*1.5+1.5 0.75–6
012 11.2 12 16 3*1.5+1.5 0.75–6
FR2 016 15 16 20 3*4+4 0.5–16 4–16
023 21.5 23 25 3*4+4 0.5–16 4–16
031 29 31 32 3*6+6 0.5–16 4–16
FR3 038 35.2 38 40 3*16+16 16–35 2.5–25
046 42.6 46 50 3*16+16 16–35 2.5–25
061 55.7 61 63 3*16+16 16–35 2.5–25
FR4 072 65.7 72 80 3*25+16 16–50 6–50
087 79.4 87 100 3*35+16 16–50 6–50
105 97 105 125 3*50+25 16–50 6–50
FR5 140 129 140 160 3*70+35 50–185 10–120
170 157 170 200 3*95+50 50–185 10–120
205 189 205 250 3*120+70 50–185 10–120
FR6 261 246.2 261 400 2*(3*70+35) 2*(50–150) 35–150
310 292.4 310 400 2*(3*95+50) 2*(50–150) 35–150