Instruction Leaflet IL040029EN
Effective December 2017
16 EATON www.eaton.com
PowerXL DH1 Series VFD
North America cable and fuse sizes—440 Vac to 500 Vac ratings
Notes
Line and motor cable size is selected according to UL 508C Table 40.3 for copper conductor rated 75 °C. Use only with copper wire rated 75 °C here.
Size requirements for other different wire types are defined in the National Electrical Code, ANSI/NFPA 70.
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 508C Table 6.4.
If power cubes or bypass are used, a UL listed Class RK5, J, T or equivalent fuse is recommended.
FR0 is not available till June 2018.
Frame size
Amp
suffix
Input current
(VT/I
L
)
NEC motor
amp rating
at 460 V
Current
(VT/I
L
)
at 40 °C
Recommended
fuse
rating
NEC
wire size (AWG)
Terminal connection
size (AWG)
Line and
motor Ground
Line and
motor Ground
FR0
3D3 3.8 3 3 10 14 14 26–10 18–10
4D3 4.3 3.4 3.4 10 14 14 26–10 18–10
5D6 6 4.8 4.8 10 14 14 26–10 18–10
7D6 9.6 7.6 7.6 15 14 14 26–10 18–10
FR1 3D3 2.8 3 3 10 14 14 26–10 18–10
4D3 3.2 3.4 3.4 10 14 14 26–10 18–10
5D6 4.5 4.8 4.8 10 14 14 26–10 18–10
7D6 7.1 7.6 7.6 10 14 14 26–10 18–10
9D0 8.4 — 7.6 15 14 14 26–10 18–10
012 10.2 11 11 15 14 14 26-10 18–10
FR2 016 13 14 14 20 12 12 20–6 12–6
023 19.6 21 21 30 10 10 20–6 12–6
031 25.2 27 27 35 8 8 20–6 12–6
FR3 038 31.7 34 34 50 6 8 6–2 14–4
046 37 40 40 60 6 8 6–2 14–4
061 48.1 52 52 80 4 6 6–2 14–4
FR4 072 59.3 65 65 100 4 4 6–1/0 10–1/0
087 70.3 77 77 110 3 4 6–1/0 10–1/0
105 87.6 96 96 125 1 3 6–1/0 10–1/0
FR5 140 114.4 124 124 175 2/0 3 1/0–350 kcmil 8–250 kcmil
170 144 156 156 200 3/0 3 1/0–350 kcmil 8–250 kcmil
205 166.1 180 180 250 250 kcmil 3 1/0–350 kcmil 8–250 kcmil
FR6 261 226.4 240 240 400 2*2/0 3 2*(1/0–300 kcmil) 3–300 kcmil
310 284.9 302 302 400 2*4/0 3 2*(1/0–300 kcmil) 3–300 kcmil