Step 4 - Start-up
POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES PUB53696—August 2020   www.eaton.com
Table 6.  Start-up wizard instructions (Cont.).
Description:
The time required for the output frequency to decelerate from maximum frequency (P1.2) to zero frequency.  When decelerating from 
different frequency levels, the deceleration time will be a fraction of the total deceleration time.
The values for the acceleration time t
1
 and the deceleration time t
2
 are calculated as follows:
t
1
=
(Max. Frequency - Min. Frequency) x Accel. Time 1
Max. Frequency
t
2
=
(Max. Frequency - Min. Frequency) x Decel. Time 
Max. Frequency
 (Hz)
t (s)
out
Min.
Frequency
Max.
Frequency
Accel. Time 1
Decel. Time 1
t
1
t
2
Min.
Frequency
P1.13
b
Remote control place
ID 135
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = IO terminal;
1 = Fieldbus; or
3 = Keypad.
Description:
Selects where the drive will look for the start command in the remote location: I/O terminals would be from the digital hard-wired 
inputs; fieldbus would be a communication bus; and keypad display will indicate what mode is selected
P1.14
ab
Remote reference
ID 137
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = AI;
1 = Drive reference pot;
2 = AI joystick;
3 = Motor pot;
4 = Maximum frequency;
5 = PI control output;
6 = Keypad; or
7 = Fieldbus reference.
Description:
This parameter determines the reference for remote 1 control mode.  This value can be fed from an analog input, keypad, or fieldbus 
reference signal
P13.5.3
Keypad lock PIN
ID 75