Instruction Book IB182071EN
July 2018
Remote Power Racking System
(RPR-2)
www.eaton.com
The “hook” on the handle will need to be positioned behind the
clutch handle. (Figure C.6)
17) Insert the retaining clip between the “hook” and the clutch
handle. (Figure C.7)
18) Attach the vertical control box to a convenient location in
the switchgear. The control box has magnets to allow easy
attachment to the switchgear. (Figure C.8)
19) Connect the motor plug from the vertical control box into the
switchgear female motor connection plug. (Figure C.9)
20) Position the RPR-2 in front of the cell, near the racking adapter
Figure C.5. Installing Racking Adapter Housing
Figure C.6. Attaching Pull Back Housing
Figure C.7. Attaching Retaining Clip
Figure C.8. Installing Racking Adapter Housing
Figure C.9. Connecting Vertical Control Box Motor Plug