Appendix E—Motor/Application Considerations
S811+ Soft Starter MN03900001E—November 2012 63
Appendix E—Motor/Application Considerations
Squirrel Cage Motor
This is the most common application.
The motor is configured with three motor leads available.
In this case, wire the motor to the soft starter with one lead 
per phase, observing proper phase rotation. An in-sight 
disconnect means should be installed, per code 
requirements.
Wye-Delta Motor 
The wye-delta motor is a traditional way of achieving a 
reduced voltage start using regular contactors and starters. 
In this method, the motor is constructed with all six leads 
brought out to connect the unit in a wye configuration. This 
allows about 58% of the current (33% starting torque) to be 
applied during start-up. A timer is used to control the circuit 
and switch to the delta configuration as the unit approaches 
full speed.
In this case, wire the six-lead motor in a standard delta 
configuration. The soft starter is then used to control the 
voltage and motor torque without the need for additional 
circuitry. An insight disconnect means should be installed, 
per local code. The S811+ Soft Starter must be wired into 
the three-phase line feeding the three main motor input leads 
as would be done for normal across-the-line starting. It must 
not be wired internally between motor windings in an 
inside-the-delta configuration.
Part Winding Motor 
The part winding motor is another design created to help 
achieve a soft start to the load. A part winding motor is 
constructed of two separate (but parallel) windings. When 
using a traditional starter, the first winding would receive full 
voltage. This winding supplies as much as 400% of the 
motors FLA; about 45% starting torque in a delta 
configuration for motor startup. After a timed delay, full 
voltage is applied to the second winding. The second 
winding acts in parallel with the first to provide for normal 
running current. Part winding motors are available in both a 
wye and delta configuration, dependent upon the 
manufacturer. Refer to the motor nameplate for the correct 
wiring information. In this case, wire the two windings in 
parallel. The soft starter is then used to control the current 
applied to the motor. An in-sight disconnect means should 
be installed, per code requirements.
Dual Voltage Motor
A dual voltage motor should be wired into the appropriate 
configuration for the line voltage it is being applied to. Refer 
to the motor nameplate for the correct wiring information. 
The soft starter must be selected for the appropriate line 
voltage.
Multi-Speed Motor
Some motors have multiple windings to allow operation at 
different base speeds. The multiple speeds are sometimes 
utilized for soft starting and other times for a process 
requirement of the machine to which it is attached. If only 
one speed is required, the motor should be wired for that 
speed. If multiple speeds are required, the appropriate 
contactors will need to be connected to the output of the 
Soft Starter. The contactors must be in the selected speed 
position before the soft starter is started. The motor must be 
stopped and the soft starter turned off before the speed 
selection contactors are changed.
Other Winding Configurations
Motors with other winding configurations, designed for 
specific characteristics, should be wired in a fashion 
consistent with their intended use. The motor nameplate 
contains information on the available configurations. The 
motor winding configuration chosen must be appropriate for 
the available line voltage. The soft starter must also be 
selected on the basis of the configuration chosen.
Power Factor Correction Capacitors
Power factor correction capacitors should be installed on the 
line side of the soft starter. It is recommended that at least 
10 feet of cable be between the capacitor and the soft 
starter. The power factor correction capacitors can be 
switched with a separate contactor. NEMA ICS2-1988 Part 
2-210.81.01 provides recommendations for when a separate 
contactor should be used to switch the power factor 
correction capacitor including high inertia loads, reversing 
motors, frequently jogged motors and multi-speed motors.
It is not recommended that the power factor correction 
capacitors be used on the load side of the soft starter. If used 
on the load side, the overload relay will measure the 
combination of capacitor and motor current causing the 
overload relay to not function correctly.