Page 10 (60) Motor Pump Enhanced Protection Application SV9000
Group 3, Output and supervision parameters
Cod
e
Parameter Range Step Default Custom Description Page
3.1 Analog output function 0—11 1 1 0 = Not used Scale 100%
1 = O/P frequency (0—f
max
)
2 = Motor speed (0—max. speed)
3 = O/P current (0—2.0 x I
nSV9
)
4 = Motor torque (0—2 x T
nSV9
)
5 = Motor power (0—2 x P
nSV9
)
6 = Motor voltage (0—100% x U
nM
)
7 = DC-link volt. (0—1000 V)
8 = Input signal V
in
9 = Input signal I
in
10 =Reference frequency
11 =Reference torque
24
3.2 Analog outp. filter time 0.01—10 s 0.01 1.00 24
3.3 Analog outp. inversion 0—1 1 0 0 = Not inverted
1 = Inverted
24
3.4 Analog output minimum 0—1 1 0 0 = 0 mA
1 = 4 mA
25
3.5 Analog output scale 10—1000% 1% 100% 25
3.6 Output freq. limit 1
supervision function
0—2 1 0 0 = No
1 = Low limit
2 = High limit
25
3.7 Output freq. limit 1
supervision value
0—f
max
(par. 1. 2)
0.1
Hz
0 Hz 25
3.8 Output freq. limit 2
supervision function
0—2 1 0 0 = No
1 = Low limit
2 = High limit
25
3.9 Output freq. limit 2
supervision value
0—f
max
(par.1. 2)
0.1
Hz
0 Hz 25
3.10 Torque limit supervision
function
0—2 1 0 0 = No
1 = Low limit
2 = High limit
26
3.11 Torque limit supervision
value
0—200%
xT
nSV9
1% 100% 26
3.12 Reference limit
supervision function
0—2 1 0 0 = No
1 = Low limit
2 = High limit
26
3.13 Reference limit
supervision value
0—f
max
(par. 1. 2)
0.1
Hz
0 Hz 26
3.14 Extern. brake Off-delay 0—100.0 s 0.1 s 0.5 s 26
3.15 Extern. brake On-delay 0—100.0 s 0.1 s 1.5 s 26
3.16 Frequency converter
temperature limit
supervision function
0—2 1 0 0 = No
1 = Low limit
2 = High limit
27
3.17 Frequency converter
temperature limit value
-10—+75°C 1°C +40°C 27
3.18 I/O-expander board (opt.)
analog output content
0—9 1 3 See parameter 3. 1 27
3.19 I/O-expander board (opt.)
analog output filter time
0.01—10 s 0.01 1.00 See parameter 3. 2 27
3.20 I/O-expander board (opt.)
analog output inversion
0—1 1 0 See parameter 3. 3 27
3.21 I/O-expander board (opt.)
analog output minimum
0—1 1 0 See parameter 3. 4 27
3.22 I/O-expander board (opt.)
analog output scale
10—1000% 1 100% See parameter 3. 5 27
3.23 Analog output offset
(basic control board)
-100% —
100.0%
1 100% 27
3.24 I/O-expander board (opt.)
analog output offset
-100% —
+100.0%
1 100% 27