SV9000 Motor Pump Enhanced Protection Application Page 11 (60)
Group 4, Drive Control Parameters
Code Parameter Range Step Default Custom Description Page
4.1 Acc./Dec. ramp 1 shape 0—10 s 0.1 s 0
0 = Linear
>0 = S-curve acc./dec. time
28
4.2 Acc./Dec. ramp 2 shape 0—10 s 0.1 s 0
0 = Linear
>0 = S-curve acc./dec. time
28
4.3 Acceleration time 2 0.1—3000 s 0.1 s 10 s 28
4.4 Deceleration time 2 0.1—3000 s 0.1 s 10 s 28
4.5 Brake chopper 0—1 1 0
0 = Brake chopper not in use
1 = Brake chopper in use
2 = External brake chopper
28
4.6 Start function 0—1 1 0
0 = Ramp
1 = Flying start
29
4.7 Stop function 0—1 1 0
0 = Coasting
1 = Ramp
29
4.8 DC-braking current
0.15—1.5
x I
nSV9
(A)
0.1 A
0.5 x
I
nSV9
29
4.9 DC-braking time at Stop 0—250.0 s 0.1 s 0 s 0 = DC-brake is off at Stop 29
4.10
Execute freq. of DC-
brake during ramp Stop
0.1—10 Hz
0.1
Hz
1.5 Hz 30
4.11 DC-brake time at Start 0.0—25.0 s 0.1 s 0 s 0 = DC-brake is off at Start 30
4.12
Multi-step speed
reference 1
f
min
—f
max
(1. 1) (1. 2)
0.1
Hz
10 Hz 31
4.13
Multi-step speed
reference 2
f
min
—f
max
(1. 1) (1. 2)
0.1
Hz
15 Hz 31
4.14
Multi-step speed
reference 3
f
min
—f
max
(1. 1) (1. 2)
0.1
Hz
20 Hz 31
4.15
Multi-step speed
reference 4
f
min
—f
max
(1. 1) (1. 2)
0.1
Hz
25 Hz 31
4.16
Multi-step speed
reference 5
f
min
—f
max
(1. 1) (1. 2)
0.1
Hz
30 Hz 31
4.17
Multi-step speed
reference 6
f
min
—f
max
(1. 1) (1. 2)
0.1
Hz
40 Hz 31
4.18
Multi-step speed
reference 7
f
min
—f
max
(1. 1) (1.
2)
0.1
Hz
50 Hz 31