Page 14 (60) Motor Pump Enhanced Protection Application SV9000
Group 8, Autorestart parameters
Code Parameter Range Step Default Custom Description Page
8.1
Automatic restart:
number of tries
0—10 1 0 0 = not in use 42
8.2
Automatic restart:
trial time
1—6000 s 1 s 30 s 42
8.3
Automatic restart:
start function
0—1 1 0
0 = Ramp
1 = Flying start
42
8.4
Automatic restart of
undervoltage
0—1 1 0
0 = No
1 = Yes
42
8.5
Automatic restart of
overvoltage
0—1 1 0
0 = No
1 = Yes
42
8.6
Automatic restart of
overcurrent
0—1 1 0
0 = No
1 = Yes
42
8.7
Automatic restart of
reference fault
0—1 1 0
0 = No
1 = Yes
42
8.8
Automatic restart after
over/undertemperature
fault
0—1 1 0
0 = No
1 = Yes
42
Group 9, Torque Control
Code Parameter Range Step Default Custom Description Page
9.1
Torque reference
selection
0—2 1 0
0 = None
1 = V
in
2 = I
in
44
9.2
Torque reference scaling
bias
-100% —
+100%
1 0 0 = not in use 44
9.3
Torque reference scaling
gain
-320% —
+320%
1 100 100 = no scaling 44
9.4 TC time constant 1—1000 ms 1 ms 128 ms 44
9.5 TC min. control limit 0—10.00 Hz
0.01
Hz
3.00 Hz 44