SV9000 Motor Pump Enhanced Protection Application Page 15 (60)
Group 10, Fieldbus Parameters
Code Parameter Range Step Default Custom Description Page
10.1 Fieldbus control select 0—1 1 0
0 = Control via I/O terminals
1 = Control via Fieldbus board
45
10.2 MODBUS Slave address 1—247 1 1 45
10.3 Baud rate 1—7 1 6
1 = 300 baud
2 = 600 baud
3 = 1200 baud
4 = 2400 baud
5 = 4800 baud
6 = 9600 baud
7 = 19200 baud
45
10.4 MB Parity type 0ó 2 1 0
0 = None
1 = Even
2 = Odd
45
10.5 Modbus time-out 0ó 3600 s 1 s 0 s 0 = No time-out 45
10.6 Profibus slave address 2ó 126 1 2 45
10.7 Profibus baud rate 1ó 10 1 10
1 = 9.6 kbaud
2 = 19.2 kbaud
3 = 93.75 kbaud
4 = 187.5 kbaud
5 = 500 kbaud
6 = 1.5 Mbaud
7 = 3 Mbaud
8 = 6 Mbaud
9 = 12 Mbaud
10 = AUTO
46
10.8 Profibus PPO Type 1ó 4 1 1
1 = PPO 1
2 = PPO 2
3 = PPO 3
4 = PPO 4
46
10.9 Profibus Process Data 1 0ó 99 1 1 46
10.10 Profibus Process Data 2 0ó 99 1 2 46
10.11 Profibus Process Data 3 0ó 99 1 3 46
10.12 Profibus Process Data 4 0ó 99 1 99 46
10.13 LonWorks Service Button 0ó 1 1 0 46