Page 16 (60) Motor Pump Enhanced Protection Application SV9000
Group 11, Digital Input Parameters
Code Parameter Range Step Default Custom Description Page
11.1DIA2 function01510
0 = Not Used
1 = Ext. Fault, Closing Contact
2 = External Fault, Opening Contact
3 = Run Enable
4 = Acc./Dec. Time Selection
5 = Reverse
6 = Jogging Speed
7 = Fault Reset
8 = Acc./Dec. Operation Prohibit
9 = DC-Braking Command
10 = Torque Control
11 = Hot Motor Winding - Open Contact
12 = Hot Motor Bearing - Open Contact
13 = Seal Leak Detection - Closed Contact
14 = High Vibration - Closed Contact
15 = Multi-Step Speed Select 1
47
11.2
DIB4 function
(terminal 14)
01410
0 = Not used
1 = Ext. fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Acc./dec. time selection
5 = Reverse
6 = Jogging speed
7 = Fault reset
8 = Acc./dec. operation prohibit
9 = DC-braking command
10 = Torque Reference Signal
11 = Hot Motor Winding - Open Contact
12 = Hot Motor Bearing - Open Contact
13 = Seal Leak Detection - Closed Contact
14 = High Vibration - Closed Input
48
15 = Multi-Step Speed Select 2
11.3
DIB5 function
(terminal 15)
014 10
0 = Not used
1 = Ext. fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Acc./dec. time selection
5 = Reverse
6 = Jogging speed
7 = Fault reset
8 = Acc./dec. operation prohibit
9 = DC-braking command
10 = Motorized Pot Speed Up
11 = Seal Leak Detection - Open Contact
12 = High Vibration - Open Contact
13 = Hot Motor Winding - Closed Contact
14 = Hot Motor Bearing - Closed Contact
48
15 = Multi-Step Speed Select 3
11.4
DIB6 function
(terminal 16)
01110
0 = Not used
1 = Ext. fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Acc./dec. time selection
5 = Reverse
6 = Jogging speed
7 = Fault reset
8 = Acc./dec. operation prohibit
9 = DC-braking command
10 = Motorized Pot Speed Down
11 = Seal Leak Det. - Open Contact
12 = High Vibration - Open Contact
13 = Hot Motor Winding - Closed Contact
14 = Hot Motor Bearing - Closed Contact
48

Other manuals for Eaton SV9000