Page 16A (60) Motor Pump Enhanced Protection Application SV9000
Group 11, Digital Input Parameters
Code Parameter Range Step Default Custom Description Page
11.5
DIC1 function 0ā15 10
0 = Not used
1 = Ext. fault, closing contact
2 = External fault, opening contact
3 = Run enable
4 = Acc./dec. time selection
5 = Reverse
6 = Jogging speed
7 = Fault reset
8 = Acc./dec. operation prohibit
9 = DC-braking command
10 = Multi-Step Speed Select 1
11 = Motorized pot. speed up
12 = Hot Motor Winding - Open Contact
13 = Hot Motor Bearing - Open Contact
14 = Seal Leak Detection - Closed Contact
15 = High Vibration - Closed Contact
48
s
s
s
s
11.7 Hot Motor Winding Delay 0
-
600.0 0.1 2.0 0 = Delay not in use 49
11.8 Hot Motor Bearing Delay 0-600.0
0.1 2.0 0 = Delay not in use 49
11.9
Seal Leak Detection
Delay
0-600.0 0.1 2.0 0 = Delay not in use 49
11.10 High Vibration Delay 0-600.0 0.1 2.0 0 = Delay not in use 49
11.
6
DIC2 function 0 ā 15 10
0 = Run Enable Open
1 = Ext. fault, closing contact
2 = External fault, opening contact
3 = Run Enable, Close
4 = Acc./dec. time selection
5 = Reverse
6 = Jogging speed select
7 = Fault reset
8 = Acc./dec. operation prohibit
9 = DC-braking command
10 = Multi-Step Speed Select 2
11 = Motorized pot. speed down
12 = Hot Motor Detection -
Open Contact
13 = Hot Motor Bearing -
Open Contact
14 = Seal Leak Detection -
Closed Contact
15 = High Vibration - Closed Contact
48