SV9000 Motor Pump Enhanced Protection Application Page 17 (60)
Group 12, Digital Output Parameters
Code Parameter Range Step Default Custom Description Page
12.1 Digital output function 0—22 1 1
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = SV9000 overheat warning
6 = External fault or warning
7 = Reference fault or warning
8 = Warning
9 = Reversed
10 = Jogging speed selected
11 = At speed
12 = Motor regulator activated
13 = Output freq. limit superv. 1
14 = Output freq. limit superv. 2
15 = Torque limit supervision
16 = Reference limit supervision
17 = External brake control
18 = Control from I/O terminals
19 = Frequency converter
temperature limit supervision
20 = Unrequested rotation direction
21 = External brake control inverted
22 = Thermistor fault or warning
50
12.2Relay output function0—2212Same as below (parameter 12. 3)50
12.3 Relay 2 output function 0—26 1 3
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = SV9000 overheat warning
6 = External fault or warning
7 = Reference fault or warning
8 = Warning
9 = Reversed
10 = Jogging speed selected
11 = At speed
12 = Motor regulator activated
13 = Output freq. limit superv. 1
14 = Output freq. limit superv. 2
15 = Torque limit supervision
16 = Reference limit supervision
17 = External brake control
18 = Control from I/O terminals
19 = Frequency converter
temperature limit supervision
20 = Unrequested rotation direction
21 = External brake control inverted
22 = Thermistor fault or warning
23 = Hot Motor Winding Fault
24 = Hot Motor Bearing Fault
25 = Seal Leak Detection Fault
26 = High Vibration Fault
50
12.4 Relay 3 output function 0—26 1 0 Same as above (parameter 12. 3) 50
Update Note:
2
Update Note:
3
12.5 Relay 4 output function 0—26 1 0 Same as above (parameter 12. 3) 50
12.6 Relay 5 output function 0—26 1 0 Same as above (parameter 12. 3) 50
12.7
Digital output DO1
on delay
0—600.0 s 0.1 s 0 0 = delay not in use 51
12.8
Digital output DO1
off delay
0—600.0 s 0.1 s 0 0 = delay not in use 51
12.9
Relay output RO1
on delay
0—600.0 s 0.1 s 0 0 = delay not in use 51
12.10
Relay output RO1
off delay
0—600.0 s 0.1 s 0 0 = delay not in use 51
12.11
Relay output RO2
on delay
0—600.0 s0.1 s 2.0 0 = delay not in use51
2.02.0