SVX9000 Drives
MN04003009E—November 2011 www.eaton.com
8
STEP 4 (Continued)
Operate Menu — M8
The Operate Menu provides a easy to use method of viewing key numerical
Monitoring Menu items. Some applications also support the setting of
reference values in this menu. The items displayed vary by application. The
table below is an example for the Standard application.
Operate Menu Items — Standard Application Example
The menu is navigated by using the left and right arrow buttons. If a
reference level is available for setting, the up and down arrow buttons adjust
the value. To exit the Operate Menu to access the other menus, depress the
ENTER button for 2 seconds. While in the other menus, if there is no keypad
activity, the display will return to the Operate Menu after 30 seconds.
Code Signal Name Unit Description
O.1 Output Frequency Hz Output frequency
O.2 FreqReference Hz Frequency reference
O.3 Motor Speed rpm Calculated motor speed
O.4 Motor Current A Measured motor current
O.5 Motor Torque % Calculated torque based on nominal motor
torque
O.6 Motor Power % Calculated power based on nominal motor
power
O.7 Motor Voltage V Calculated motor voltage
O.8 DC-Bus Voltage V Measured DC-bus voltage
O.9 Unit Temperature °C Heatsink temperature
O.10 MotorTemperature % Calculated motor temperature based on the
motor nameplate information and the
calculated motor load
R1 Keypad Reference Hz Keypad frequency reference setting
MN04003009E.fm Page 8 Wednesday, November 9, 2011 8:47 AM