65A7355H01 November 2011 www.eaton.com
Table 4-4: Inspection Process Chart
Drive insulator,
barriers, and stand-off
insulators
Clean with lint-free cloth or
replace cracked piece
Clean and retest or replace
Between main circuit
terminals
Clean and retest or replace
Control circuit to
ground
Clean and retest or replace
Proceed with
integrity check
If integrity check is not
satisfactory, replace
encapsulated pole unit
assembly
Resistance less
than Table 4-2
values
Contact Eaton rep. for
recommendations
No burning or
damage or spring
discoloration
Replace if burned, damaged,
eroded or discolored
Shunt (Closing and
Opening) release,
including disconnects
Smooth and correct
operation by control
power
Test closing and
tripping of the circuit
breaker twice
Replace any defective parts
Securely tied in
proper place
Repair or tie as necessary
Tighten or replace if
necessary
No loose or missing
parts
No dust or foreign
object
Smooth operation
and no excessive
wear
Contact Eaton rep. for
recommendations
Deformation or
Excessive Wear
No excessive
deformation or wear
Remove cause and/or replace
parts
Manual charging,
closing, and tripping
Correct per troubleshooting
chart 6.9