52
65A7355H01 November 2011 www.eaton.com
6.6 Opening
The opening operation is accomplished by either
manually pushing the “open” button or connecting the
external power supply to actuate the shunt opening
release coil. The breaker uses a hydraulic damper to
help absorb some of the opening force. Once the
breaker is open, the indicator will display “OPEN”.
6.7 Control Schemes
Refer to Fig. 6-10 for the W-VACi circuit breaker
diagram.
6.8 Selective Parts Configuration
The voltages for the secondary control circuit can be:
24-48-60-110-125-220-250 VDC and 120-220-230
VAC.
Configurations and electrical parameters for selective
parts are presented in the next few sections.
Rated Parameters of UMA Motor
1
Item
Unit
Value
Rated
Voltage
VDC (Ua)
24
48
60
110/125
220/250
Rated
Voltage
VAC (Ua)
-
-
-
110/120
220/230
Voltage
Range
% (Ua)
85-110
Time for
Charging (S)
(s)
15
Rated Parameters of Releases
1
Item
Unit
Value
Rated
Voltage
VDC (Ua)
24
48
60
110/125
220/250
Rated
Voltage
VAC (Ua)
-
-
-
110/120
220/230
Rated
Current
(A)
10
5
5
3
2
Shunt
Closing
Release
Voltage
Range*
% (Ua)
85-110
Shunt
Opening
Release
Voltage
Range
% (Ua)
70-110
Rated Parameters of Undervoltage Releases
1
Item
Unit
Value
Rated
Voltage
Ua (VDC)
24
48
60
110/125
220/250
Rated
Voltage
Ua (VAC)
-
-
-
110/120
220/230
UVR
Operates,
& Circuit
Breaker
Opens
Limits
% (Ua)
0-35
UVR does
not operate
Limits
% (Ua)
70-110
Rated Parameters of Electromagnetic Interlock
1
Item
Unit
Value
Rated
Voltage
Ua (VDC)
24
48
60
110/125
220/250
Rated
Voltage
Ua (VAC)
-
-
-
110/120
220/230
Operating
Limits
% (Ua)
85-110
Continuous
Power (Pc)
W (VDC)
5
VA (VAC)
5
1
Insulation voltage for all electronic parts is 2000 V 50/60 Hz
(for 1 min.)