4.8 Troubleshooting Chart
Symptom
Inspection area
Probable cause
Fail to Close
Closing-spring
not charged
Motor Circuit
No control power
fuse blown or switch off
Secondary disconnect is not connected
Motor cut-off switch or its push lever is damaged
● Loose wire terminal connections
Motor failure
Closing-spring
charged but breaker
does not close
Shunt Closing Release circuit,
when the plunger of the shunt
does not pick up
● No control power, or its out of voltage range
fuse blown or switch off, or wrong voltage applied)
Secondary disconnects is not in service
Anti-pumping device is in service
Shunt closing release failure
The breaker is between service and test position
when it is in the switchgear
Mechanical Interlock, may
override the plunger of the shunt
close release may pick up
The breaker is between service and test position
when it is in the switchgear
Closing spring is released, but
the breaker fails to close.
Trip circuit is energized (trip free)
● Trip latch does not reset
Breaker does not
close when manually
pushing the close
button
Electromechanical Interlock
Secondary Disconnect is not pluged in or has no
control power to it
Breaker does not
rack in
Electromechanical Interlock
Check to see if proper secondary control voltage
is applied to the interlock