65A7355H01 November 2011 www.eaton.com
Symptom
Inspection area
Probable cause
Undesirable Close
Undesirable Close
Control Circuit
● Shunt closing release circuit is energized
● Auxiliary switch does not switch properly
Mechanism
Close release latch(does not reset)
Close button does not reset in time
Fail to Trip
Breaker does not trip
Shunt trip release circuit
● No control power, or its voltage is out of range
fuse blown or switch off, or wrong voltage applied)
Secondary disconnect is not connected
Mechanism
Entire mechanism non functional
Vacuum Interrupter
● One or more welded
Undesirable Trip
Undesirable Trip
Control Circuit
● Shunt trip circuit is energized
● Auxiliary switch does not switch properly
Mechanism
● Trip latch is damaged
● Trip latch does not reset
● Manual trip push button “O” does not reset