8.7.18 PC 45 (Outdoor unit IR chip drive failure) diagnosis and solution
Description: When the IR chip detects its own parameter error, the LED displays the failure code when
power on.
Recommended parts to prepare:
• Inverter module PCB.
Troubleshooting and repair:
Power off,then restart the
unit 2 minutes later.
Replace the inverter module PCB.
Yes
8.7.19 PC 0L (Low ambient temperature protection)
Description: It is a protection function. When compressor is off, outdoor ambient temperature(T4) is lower than -
31℉ for 10s, the AC will stop and display the failure code.
When compressor is on, outdoor ambient temperature(T4) is lower than -40℉ for 10s, the AC will stop and
display the failure code.
When outdoor ambient temperature(T4) is no lower than -26℉ for 10s, the unit will exit protection.