1.Remote Maintenance
Electrical Circuit
Refrigerant Circuit
Possible causes of trouble
Power failure
The main power tripped
Loose connections
Faulty transformer
The voltage too high or too low
The remote control is powered off
Borken the remote control
Diety air filter
Dirty condenser fins
The setting temp is higher or lower than the
room’s(cooling/heating)
The ambient temp is too high/low when the mode is
cooling/heating
Fan mode
SILENCE function is activated(optional)
Frosting and defrosting frequently
Unit will not start
The power switch is on but fans will not start
The temperature on the display board cannot be
set
Unit is on but the wind is not cold(hot)
Unit runs, but shortly stops
The unit starts up and stops frequently
Unit runs continuously but insufficient
cooling(heating)
Cool can not change to heat
Unit is noisy
Test method / remedy
Test voltage
Close the power switch
Inspect connection-tighten
Change the transformer
Test voltage
Replace the battery of the remote control
Replace the remote control
Clean or replace
Replace
Adjust the setting temp.
Turn on the AC later
Adjust to cool mode
Turn off the SILENCE function
Turn on the AC later