Maximum allowed current in function of the ambient temperature for installation method C.
Installation method F according table B.52.1.
Single-core cables, touching in free air
Clearance to wall not less than one cable
diameter.
Maximum allowed current in function of the ambient temperature for installation method F
Calculation method for IEC:
Single supply cables (3 phases + PE - configuration (1)):
Add 10 % to the total pump current (ItotPack or ItotFF from the tables)
Install the prescribed fuse on each cable
Parallel supply cable (2 x 3 phases + PE - configuration (2)):
Add 10 % to the total pump current (ItotPack or ItotFF from the tables) and divide by 2
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 phases + PE as in (3):
Add 10 % to the total pump current (ItotPack or ItotFF from the tables) and divide by √3
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))