UPS MKD700/1000 Manual
MKD Series
Page 38 of 41
14 Technical data
14.1 Specifications
Model:
MKD700
MKD1000
Power:
700 VA / 490 W
1000 VA / 700 W
Mains input:
Phases
1 external conductor + neutral conductor
Voltage window
160 300 V AC
Bypassing area
176 253 +/-20V AC
Nominal frequency
50 / 60 Hz
Power factor
> 95 %
UPS output:
Nominal voltage
230 V AC (sinus)
Power output max.
3,0 A
4,3 A
Voltage regulation
+/- 2 % (statically)
Frequency tolerance
+/- 0.5 % (battery service)
Overload
105 ... 150 % for 30 s, > 150 % for 200ms
Autonomy time
ca. 11 min (normal
conditions)
ca. 7 min (normal
conditions)
Efficiency factor:
DC -> AC
> 90 %
DC-input
Input voltage
36 V DC (nominal)
36 V DC (nominal)
Interface:
RS232
D-SUB socket 9-pol
(galvanically separated)
Environment:
Allowed temperature
0 ... + 40 °C
Suggested temp.
+15 ...+ 25 °C
Storage temp.
0 ... +40 °C
Rel. air humidity
20 ... 90 % (non condensing)
Standards:
EN 50091-2
Generally:
Technology
non-stop service, double-converter with
autom. bypass switch.
Cooling
Fan cooling
Acoustic level
< 50 dB
Weight
15.0 kg
15.0 kg
Inspections
CE
Dimensions:
h x w x d
2HE x 19“ x 415 mm
2HE x 19“ x 415 mm

Related product manuals