4. Installation
22
To minimize current loss in the leads, the following
cross section is recommended, should the battery
charging cable be insufficient:
Length [m] min. cross section
< 5 m 2.5 mm²
5 – 10 m 4.0 mm²
10 – 15 m 6.0 mm²
Accessories:
Extension sense line 8 m (Art. No. 151 906 005)
Extension Power line 8 m (Art. No. 151 906 006)
Notes:
The EFOY Pro is charging the connected battery and
the battery supplies the power for the application..
The EFOY Pro can only be used to charge lead
batteries which conform to the technical
specification (see chapter 3.3, page 13).
The EFOY Pro can charge 12 V and 24 V batteries
and automatically detects the voltage of the
connected battery.
The charging parameters for the automatic mode
can be adjusted with a standard PC – see user
manual of computer interface adapter.
To protect the battery against deep discharging it is
recommended to install a low-voltage load
disconnector that disconnects the load from the
battery.