Parameters technician
Menu Line no. Selection possibilities Unit Min. Max Factory setting
Domestic hot water 1600 Operating mode - O󰀨,On,Eco O󰀨
1610 Nominal setpoint °C 8 80 55
1612 Reduced setpoint °C 8 80 40
1614 Nominal setpoint max °C 8 80 65
1620 Release - 24h/Day, Time programs HCs,
Time program 4/DHW
Time programs HCs
1630 Charging priority - Absolute, Shifting, None,
MC shifting PC absolute
MC shifting
PC absolute
1640 Legionella function - O󰀨,Periodically,Fixedweekday O󰀨
1641 Legionella function periodically - 1 7 7
1642 Legionella funct Day - Mo,Tu,We,Th,Fr,Sa,Su Montag
1644 Legionella funct time uu:mm 00:00 23:50 ---
1645 Legionella funct setpoint °C 55 95 65
1646 Legionella funct duration min 10 360 30
1647 Legionella funct circ pump - O󰀨,On On
1660 Circulating pump release - Time program 3/HCP, DHW release,
Time program 4/DHW, Time program 5
DHW release
1661 Circulating pump cycling - O󰀨,On O󰀨
1663 Circulation setpoint °C 8 80 45
1680 Optg mode changeover - None,O󰀨,On None
Consumer circuit 1 1859 Flow temp setp cons request °C 8 120 70
1874 DHW charging priority - No, Yes Yes
1875 Excess heat draw - No, Yes No
1878 Withbu󰀨er - No, Yes Ye s
1880 With prim contr/system pump - No, Yes Ye s
Consumer circuit 2 1909 Flow temp setp cons request °C 8 120 70
1924 DHW charging priority - No, Yes Yes
1925 Excess heat draw - No, Yes No
1928 Withbu󰀨er - No, Yes Yes
1930 With prim contr/system pump - No, Yes Yes
Consumer circuit 3 1959 Flow temp setpoint °C 8 45
1974 DHW charging priority - No, Yes Yes
1975 Excess heat draw - No, Yes No
1978 Withbu󰀨er - No, Yes Yes
1980 With prim contr/system pump - No, Yes Yes
Swimming pool 2055 Pool setpoint solar heating °C 8 80 26
2056 Pool setpoint producer heating °C 8 80 22
2065 Pool charging priority solar - Priority 1, Priority 2, Priority 3 Priority 3
2070 Pool temperature maximum °C 8 95 30
2080 Pool with solar - No, Yes Yes
Primary control/
System pump
2110 Flow temp min limitation °C 8 95 8
2111 Flow temp max limitation °C 8 95 80
2121 Syst pump on heat gen lock - O󰀨,On O󰀨
2130 Mixing valve boost °C 0 50 5
2132 Actuator type - 2-position, 3-position 3-position
2133 Switchingdi󰀨erential2-pos °C 0 20 2
2134 Actuator running time s 30 873 120
2135 P-Band (Xp °C 1 100 32
2136 Integral action time (Tn) HC1 s 10 873 120
2150 Primary control/System pump - Upstreamofbu󰀨er,Downstreamofbu󰀨er Downstreamofbu󰀨er