EasyManua.ls Logo

elco Combi 24 - Page 54

elco Combi 24
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
Commissioning
Combustion analysis
Low load (Step 2/3)
Step 2: O
2
/ CO
2
check on low load
Setting the low load
The low load of the boiler can be set by
you as follows:
- Push the button “D” once (OK
buttonforconrmation)untilthe
number “100%” blinks.
- Turn the rotating button
“C” (temperature control /
menu selection button) in a
counterclockwise direction, until the
number “0%” is displayed.
- Push the button “D” once (OK) until
the number “0” no longer blinks.
Now the equipment unit will operate
at low load (0%).
- Use the measuring tool to carry out
a O
2
/CO
2
control measurement.
The detected values must lie in the
measuring range shown below.
The O
2
value at low load must lie
higher than the CO
2
value at full load.
The measuring procedure must be
carried out, until a constant measuring
result is achieved. Please take up
contact with ELCO, if the values should
lie outside of the applicable tolerances.
Switching o󰀨
- Push the button “I” and keep
the button pressed until the stop
functionswitcheso󰀨.Thestandard
display appears.
The maximum operating time of
the stop function is 4 hours without
interruption.
a
M
A
H
B C D E F
I
L
G
Legend:
A On/O󰀨switch
B Back button (ESC)
C Room temperature control button
D Conrmationbutton(OK)
E Function button for manual
operation
F Chimney sweep function button
G Info button
H Reset button
I Operation mode button for heating
circuit(s)
L Display
M Operating mode button for DHW
Legend
a Measuring point of the waste
gas probe
O
2
/ CO
2
check on low load (Step 2)
Low load Natural gas E (G20), LL (G25) Propane (G31)
O
2
Minimal 0,5% higher than measured on full load Minimal 0,2% higher than measured on full load
Maximum 7,5% Maximum 7,3%
CO
2
Minimal 0,3% lower than measured on full load Minimal 0,1% lower than measured on full load
Minimum 7,5% Minimum 8,9%
Values are valid with closed cover/air box.

Related product manuals