70
Operation
Parameter listing
Menu
Submenu
Parameter
Name Description Range
Factory
settings
26..32. Commercial Boiler - Slave 1..
26..32. 0 General
26..32. 0. 0 Engines Number
26..32. 0. 2 Maximum Water temp °C 95
26..32. 0. 3 Max CH Adjustable % 100
26..32. 0. 4 Fan inc percentage 4
26..32. 0. 5 Altitude m 0
26..32. 0. 6 Boiler tank solar integration 0
26..32. 0. 7 Emergency setpoint °C 45
26..32. 3 Water Circulation
26..32. 3. 0 Max PWM Pump % 95
26..32. 3. 2 Min PWM Pump % 45
26..32. 3. 3 CH pump overrun min 5
26..32. 5 Domestic Hot Water
26..32. 5. 0 DHW Setpoint Temperature 40 - 65°C 65
26..32. 5. 1 Comfort Function
0 = Disabled
1 = Time Based
2 = Always Active
0 - 2 0
26..32. 5. 2 System DHW Mode
0 = CH Only
1 = DHW Tank NTC
2 = DHW Tank Thermostat
0 - 2 0
26..32. 5. 3 Boiler DHW Mode
0 = CH Only
1 = DHW Tank NTC
2 = DHW Tank Thermostat
0 - 2 0
26..32. 5. 4 Anti-legionella Function
0 = OFF
1 = ON
0 - 1 0
26..32. 5. 5 Boiler DHW Charging Type
0 = Recharging
1 = Full charging
2 = Full charging Legio
0 - 2 0
26..32. 5. 6 System DHW Charging Type
0 = Recharging
1 = Full charging
2 = Full charging Legio
0 - 2 0
26..32. 5. 7 Boiler DHW Circulating Pump Release
0 = Release
1 = Time Programs
2 = Circ Pump special Time Programs
0 - 2
0
26..32. 5. 8 System DHW Circulating Pump Release
0 = Release
1 = Time Programs
2 = Circ Pump special Time Programs
0 - 2 0