43
Parameters technician
Menu Line no. Selection possibilities Unit Min. Max Factory setting
Conguration 6051 Voltage value 2 H2 module 1 V 0 10 0
6059 Voltage value 2 H2 module 2 V 0
6067 Voltage value 2 H2 module 3 V 0
6052 Function value 2 H2 module 1 - -1000 5000 0
6060 Function value 2 H2 module 2 - 0
6068 Function value 2 H2 module 3 - 0
6097 Sensor type collector - NTC, PT 1000 NTC
6098 Readjustm collector sensor °C -20 20 0
6100 Readjustm outside sensor °C -3 3 0
6110 Time constant building h
0 50
5
6117 Central setpoint shift °C
1 100
5
6118 Setpoint reduction delay K/min
O,1-200
20
6120 Frost protection plant -
O,On
On
6200 Save sensors -
No, Yes
No
6205 Reset to default parameters -
No, Yes
No
6212 Check nr heat source 1 -
0 199999
0
6213 Check nr heat source 2 -
0 199999
0
6215 Check nr storage tank -
0 199999
0
6217 Check nr heating circuits -
0 199999
0
6220 Software version -
0 99
0
LPB 6600 Device address -
0 239
1
6601 Segment address -
0 16
0
6604 Bus power supply function -
O,Automatically
Automatically
6605 Bus power supply state -
O,On
On
6610 Display system messages -
No, Yes
No
6612 Alarm delay min
2-60 min
10
6620 Action changeover functions -
Segment, System
Segment
6621 Summer changeover -
Locally, Centrally
Locally
6623 Optg mode changeover -
Locally, Centrally
Locally
6624 Manual source lock -
O,Automatically
Automatically
6625 DHW assignment - Local HCs, All HCs in segment,
All HCs in system
All HCs in system
6632 Note OT limit ext source -
No, Yes
No
6640 Clock mode - Autonomously, Slave without remote setting, Slave
with remote setting, Master
Autonomously
6650 Outside temp source -
0 239
0