44
Parameters technician
Menu Line no. Selection possibilities Unit Min. Max Factory setting
Errors 6700 Message -
0 65535
0
6705 SW diagnostic code -
0 65535
0
6706 Burn ctrl phase lockout pos -
0 255
0
6710 Reset alarm relay -
0 1
0
6740 Flow temp 1 alarm min
10 240
---
6741 Flow temp 2 alarm min ---
6742 Flow temp 3 alarm min ---
6743 Boiler temp alarm min ---
6745 DHW charging alarm h 1 48 ---
6800
6810
6820
6990
Time stamp error
Note 1
Note 2
.....
Note 20
h:m 00:00 23:59 04
6803
6813
6823
6993
Error code
Note 1
Note 2
.....
Note 20
- 0 9999 0
6805
6815
6825
6995
SW diagnostic code
Past value 1
Past value 2
......
Past value 20
-
0 9999 0
6806
6816
6826
6996
Burner control phase
Past value 1
Past value 2
......
Past value20
-
0 255 0
Maintenance/Special
mode
7040 Burner hours interval h
100 10000
1500
7041 Burn hrs since maintenance h
0 10000
0
7042 Burner start interval -
100 65500
9000
7043 Burn starts since maint -
0 65535
0
7044 Maintenance interval Months
1 240
24
7045 Time since maintenance Months
0 240
0
7050 Fan speed ionization current rpm
0 10000
0
7051 Message ionization current -
No, Yes
No
7130 Chimney sweep function -
O,On
O
7131 Burner output -
Partial load, Full load, Max heating load
Full load
7140 Manual control -
O,On
O
7143 Controller stop function -
O,On
O
7145 Controller stop setpoint %
0 100
50
7146 Deaeration function -
O,On
O
7147 Type of venting - None, Heating circuit continuous,
Heating circuit cycled, DHW continuous,
DHW cycled
None
7170 Telephone customer service -
0 9
0
7250 PStick storage pos -
0 250
0
7251 PStick data description -
0 255
0
7252 PStick command - No operation, Reading from stick,
Writing on stick
No operation
7253 PStick progress %
0 100
0
7254 PStick status - 0: No stick
1: No operation
2: Writing on stick
3: Reading from stick
4: EMC test active
5: Writing error
6: Reading error
7: Incompatible data set
8: Wrong stick type
9: Stick format error
10: Check data set
11: Data set disabled
12: Reading disabled
No Stick