12-24
CONTROL SYSTEM
SM OU12HP 2-E.2 GB
12.9.1.2 6HP
Name Default Value Units
MinOFFTime 3 minute
MinONTime 3 minute
HzDown1 3 Hz/min
HzDown2 10 Hz/min
DImin 30 minute
DImax 120 minute
TimeD 1 minute
DTmin 2 minute
DTmax 12 minute
DIT 10 minute
CTMRUP 15 minute
DIF 30 minute
TCT 10 second
HSTOH1 88 °C
HSTOH2 93 °C
HSTOH3 95 °C
HSTOH4 97 °C
HSTOH5 100 °C
HSTOHDelta1 -1 NA
HSTOHDelta2 1NA
EEVCVTConst 15 second
BalanceTime 1 minute
EEVInitOpen 300 step
DEICT1 60 second
DEICT2 36 second
DEICT3 6 second
EEVNormRate 33 ms/pulse
EEVHighRate 12 ms/pulse
EEVMaxOpen 500 step
DST C
DSTF 12 °C
DeiceFreqChRV 0Hz
EEVDeiceTcnst 20 second
OFBlncTime 2 minute
OFTcnst 60 second
OFMinTimeReduce 60 second