5-39
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-03
Service Manual - WNG
5.30 Pressure Curves.
5.30.1 Cooling.
Discharge Pressure VS.Outdoor Temp
10
15
20
25
30
35
40
15 20 25 30 35 40 46
Outdoor Temp.(DB
o
C )
Discharge Pressure (Bar[g])
15/21(WB/DB ºC)
17/24(WB/DB ºC)
19/27(WB/DB ºC)
21/29(WB/DB ºC)
23/32(WB/DB ºC)
Suction Pressure VS.Outdoor Temp
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
11.5
12.0
15 20 25 30 35 40 46
Outdoor Temp.(DB
o
C )
Suction Pressure (Bar[g])
15/21(WB/DB ºC)
17/24(WB/DB ºC)
19/27(WB/DB ºC)
21/29(WB/DB ºC)
23/32(WB/DB ºC)