66
Fn06 Hysteresis minimum cut-off 0…9999 10 - 10 CFBP
Fn07 Hysteresis saturation cut-off 0…9999 10 - 10 CFBP
Fn08 Enabling minimum cut-off 0…1 1 - 1 num
Fn09 Enabling saturation cut-off 0…1 1 - 1 num
Fn10 Compressor operation on request 0…1 0 - 1 num
Fn11 Enable fan rotation 0…1 0 - 0 num
Fn12 Mode for reaching maximum pick-up speed 0…1 0 - 0 num
Fn13 Fan pick-up time 0…255 2 - 5 secs
Fn14 Bypass cut-off time 0…255 80 - 80 secs
Fn15 Preventilation 0…255 0 - 0 secs
Fn16 Interstep up time 0…255 15 - 15 secs
Fn17 Interstep down time 0…255 5 - 5 secs
Fn18 Maximum time all fans can stay off 0…500 500 - 500 Hours
Fn19 Maximum hours of use for fan 0…6500 0 - 0
Hours*10
Fn20 Minimum speed 0…100 40 - 40 %
Fn21 Maximum silent speed 0…100 100 - 90 %
Fn22 Maximum speed 0…100 100 - 100 %
Fn23 Maximum pick-up speed 0…100 100 - 100 %
Fn24 Default power for non-allocated probe/probe error 0…100 100 - 100 %
Fn25 Number of fans per step for fan coil -1…4 0 - 0 num
Fn26 Fan forcing time after maximum OFF time 0…54 10 - 10 min
Al Folder
AL00 Time interval for alarm event count 1…99 60 60 60 min
AL01 Number of inlet pressure switch events 0…33 0 0 0 num