PAR. DESCRIPTION M.U. RANGE EZ-HT EZ-MT EZ-LT
dt drainage time. Coil drainage time. min 0 ... 250 5 5
dFd
Allows exclusion of the evaporator fans to be selected or not during
defrosting. n(0) = No (it depends on FCO); y(1) = Yes (fans excluded).
flag n/y y y
FCO
Allows to select compressor fans lock OFF (switched off).
H42 FCO COMPRESSOR ON COMPRESSOR OFF
H42 = y
0
Thermostat controlled OFF
1
Thermostat controlled Thermostat controlled
2
Not used Not used
3
Not used Not used
H42 = n
0
ON OFF
1
Not used Not used
2
Not used Not used
3
Not used Not used
num 0 ... 3 1 1
Att
HAL and LAL parameters mode, i.e. the absolute temperature value or
differential in relation to the setpoint.
0 = Absolute value; 1 = Relative value.
flag 0/1 0 0 0
AFd Alarms activation differential. °C/°F 1.0 ... 50.0 2.0 2.0 2.0
HAL
Temperature value (intended either as distance from setpoint or as an
absolute value based on Att) which, if exceeded in an upward direction,
triggers the activation of the alarm signal.
°C/°F
LAL ... 320
50.0 50.0 50.0
LAL
Temperature value (intended as distance from setpoint or as an absolute
value based on Att) which, if exceeded in an upward direction, triggers the
activation of the alarm signal.
°C/°F -67.0 ... HAL -50.0 -50.0 -50.0
PAO
Alarm override time after device is switched on following a power outage.
hours 0 ... 10 0 0 0
dAO Temperature alarm exclusion time after defrost. min 0 ... 999 0 0 0
OAO
Alarm signal delay (low and high temperature) after the deactivation of
the digital input (port closed).
hours 0 ... 10 0 0 0