LOCK SETPOINT MODIFICATION
The keypad can be locked by entering the 'Basic Commands' menu using and pressing and within 2 seconds, or by programming
the LOC parameter. If the keypad is locked, the 'Basic Commands' menu can be accessed and the Setpoint displayed, but the value cannot
be modified.
PAR. DESCRIPTION M.U. RANGE EZ-HT EZ-MT EZ-LT
SEt Temperature control Setpoint. °C/°F
(*)
3.0 0.0 -18.0
diF Compressor relay activation differential. °C/°F 0.1 ... 30.0 2.0 2.0 2.0
Ont
Controller switch-on time in the event of inoperable probe:
• if Ont = 1 and OFt = 0, the compressor stays on permanently (ON);
• if Ont > 0 and OFt > 0, it operates in Duty Cycle mode.
min 0 ... 250 15 15 15
OFt
Controller switch-off time in the event of a inoperable probe:
• if OFt = 1 and Ont = 0, the compressor stays off permanently (OFF);
• if Ont > 0 and OFt > 0, it operates in Duty Cycle mode.
min 0 ... 250 15 15 15
dOn Compressor relay activation delay after request. s 0 ... 250 0 0 0
dOF Delay after switching off and subsequent switch-on. min 0 ... 250 0 0 0
dbi Delay between two consecutive compressor switch-on. min 0 ... 250 0 0 0
OdO
Delay in activating outputs after the instrument is switched on or after a
power failure. 0 = Not active.
min 0 ... 250 0 0 0
dit
Interval between the start of two consecutive defrost cycles.
0 = Function disabled.
hours 0 ... 250 6 6 6
*EZ-HT: 1.0 ...18.0 °C / °F; EZ-MT: -15.0 ... 5.0 °C / °F; EZ-LT: -30.0 ... -10.0 °C / °F
PARAMETERS TABLE