PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
dF2
OUT2 activation differential. The utility stops on reaching the SP2 value
(as indicated by control probe) and restarts at a temperature value equal to
T=SP2+dF2 relative to HC2.
NTC/PTC 0.0...30.0 1.0 °C/°F
User/InstPT100-Tc 0.0...30.0 1.0 °C/°F
V/I 0...30 1 num
HS2 Maximum value assignable to setpoint SP2.
NTC/PTC
LS2...HdL
140.0 °C/°F
User/InstPT100-Tc 1350 °C/°F
V/I 199 num
LS2 Minimum value assignable to setpoint SP2.
NTC/PTC
LdL...HS2
-50.0 °C/°F
User/InstPT100-Tc -199.9 °C/°F
V/I -199 num
HA2
Maximum temperature alarm on OUT2.
(See ‘Max/Min temperature alarms’)
NTC/PTC LA2...150.0 140.0 °C/°F
User/InstPT100-Tc LA2...1999 1350 °C/°F
V/I LA2...150 150 num
LA2
Minimum temperature alarm on OUT2.
(See ‘Max/Min temperature alarms’)
NTC/PTC -150.0...HA2 -50.0 °C/°F
User/InstPT100-Tc -328...HA2 -199.9 °C/°F
V/I -150...HA2 -150 num
dn2
Switch-on delay. The indicated time must elapse between the request for
activation of the controller 2 relay and switch-on. 0 = not active.
ALL 0...250 0 min Inst
dO2
Delay time after switching off. The indicated time must elapse between
deactivation of the controller 2 relay and the next switch-on. 0 = not active.
ALL 0...250 0 min Inst
di2
Delay between switch-ons. The indicated time must elapse between two
consecutive switch-ons of regulator 2. 0 = not active.
ALL 0...250 0 min Inst
dE2
Switch-off delay. The indicated time must elapse between the request for
deactivation of the controller 2 relay and switch-off. 0 = not active.
ALL 0...250 0 min Inst
On2
Controller 2 switch-on time in the event of faulty probe.
if On2=1 and OF2=0, the controller remains on;
if On2=1 and OF2>0, the controller operates in Duty Cycle mode.
ALL 0...250 0 min Inst