PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
SAO
Alarm exclusion time until the Setpoint is reached.
0 = disabled. If SAO >0, an alarm will be generated if the Setpoint is not
reached after the time SAO (in hours).
ALL 0...10 0 hours Inst
tAO Delay preceding indication of temperature alarm. ALL 0...250 0 min Inst
AOP
Alarm output polarity. nC (0) = alarm active and output disabled
nO (1) = alarm active and output enabled
ALL nC/nO nC flag Inst
tP Enable all keys to acknowledge an alarm. n (0) = no; y (1) = yes. ALL n/y y flag Inst
COMMUNICATION (folder ‘Add’)
PtS Selection of communication protocol. t = Televis; d = Modbus. ALL t/d t flag Inst
dEA Index of the device within the family (valid values from 0 to 14). ALL 0...14 0 num Inst
FAA Device family (valid values from 0 to 14). ALL 0...14 0 num Inst
Adr Modbus protocol controller address. ALL 1...255 1 num Inst
bAU
Baudrate selection.
48 (0) = 4800; 96 (1) = 9600; 192 (2) = 19200; 384 (3) = 38400.
ALL
48/96/
192/384
96 num Inst
Pty Modbus parity bit. n (0) = none; E (1) = even; o (2) = odd. ALL n/E/o E num Inst
StP Modbus stop bit. 1b (0) = 1 bit; 2b (1) = 2 bit. ALL 1b/2b 1b flag Inst
DISPLAY (folder ‘diS’)
LOC
LOCk. Setpoint edit lock. The parameter programming menu can still be
accessed, and the settings changed, which means also that the status of this
parameter can be changed so as to unlock the keypad. n (0)= no; y (1) = yes.
ALL n/y n flag User/Inst
PS1
Password 1. When enabled (PS1 ≠ 0) it is the password to the ‘User’
parameters (User).
ALL 0...250 0 num User/Inst
PS2
Password 2. When enabled (PS2 ≠ 0) it is the password to the ‘Installer’
parameters (Inst).
ALL 0...250 15 num Inst
ndt
Display values with decimal point. n (0) = no (integers only);
y (1) = yes (displayed with decimal point); int (2) = integer.
ALL n/y/int n num User/Inst