PAR. DESCRIPTION MODEL RANGE VALUE M.U. LEVEL
CA1
Calibration 1. Positive or negative temperature value added to the value read by
Pb1, according to the setting of parameter CAI.
NTC/PTC -30.0...30.0 0.0 °C/°F
User/InstPT100-Tc -30.0...30.0 0.0 °C/°F
V/I -30...30 0 num
CAI
Intervention of the offset on display, temperature control or both.
0 = only the temperature shown is modified;
1 = sum with only the temperature used by the controllers and not for the
display, which remains unchanged;
2 = sum with the displayed temperature, which is also used by the regulators.
ALL 0/1/2 2 num Inst
LdL Minimum value that can be displayed by the device.
NTC/PTC -199.9...HdL -50.0 °C/°F
InstPT100-Tc -328...HdL -199.9 °C/°F
V/I -199...HdL -199 num
HdL Maximum value that can be displayed by the device.
NTC/PTC LdL...199.9 140.0 °C/°F
InstPT100-Tc LdL...1350 1350 °C/°F
V/I LdL...199 199 num
dro
Select the unit of measurement of probe 1.
• NTC/PTC: C (0) = °C, F (1) = °F
• PT100-Tc: C (0) = °C, F (1) = °F
• V/I: n (0) = no unit of measure selected,
t (1) = temperature, P (2) = pressure, H (3) = humidity
NTC/PTC C/F C flag
InstPT100-Tc C/F C flag
V/I n/t/P/H n num
CONFIGURATION (folder ‘CnF’) If one or more parameters are changed, the controller MUST be switched off and switched on again.
H00
Probe type selection.
• NTC/PTC: Ptc (0) = PTC, ntC (1) = NTC
• PT100-Tc: Jtc (0) = TcJ, Htc (1) = Tck, Pt1 (2) = PT100.
• V/I: 420 (0) = 4...20mA, 020 (1) = 0...20mA, t10 (2) = 0...10V,
t05 (3) = 0...5V, t01 (4) = 0...1V.
NTC/PTC Ptc/ntC ntc flag
User/Inst
PT100-Tc Jtc/Htc/Pt1 Jtc num
V/I
420/020
t10/t05/t01
420 num
H01
Output link:
0 = independent; 1 = dependent; 2 = Neutral Zone (or window).
ALL 0/1/2 0 num Inst