PAR. DESCRIPTION RANGE App1 App2 App3 App4 M.U.
CA2 Calibration 2. Temperature value to be added to the Pb2 value -12,0...+12,0 0,0 0,0 0,0 0,0 °C/°F
CA3 Calibration 3. Temperature value to be added to the Pb3 value -12,0...+12,0 0,0 0,0 0,0 0,0 °C/°F
ddL
Display mode during defrost.
0= display the temperature recorded by Pb1;
1 = lock recorded value of Pb1 at defrost start; 2 = display the “dEF” label
0/1/2 0 0 0 0 num
Ldd Timeout value for display unlock - dEF label 0 ... 255 30 30 30 30 min
dro
Select the unit of measurement used when displaying the temperature recorded by the
probes. (
0 = °C, 1 = °F).
NOTE: switching between °C and °F or vice-versa DOES NOT modify the SEt, diF
values, etc. (e.g. Setpoint=10°C becomes 10°F)
0/1 0 0 0 0 flag
ddd
Selects the type of value to display.
0 = Setpoint; 1 = probe Pb1; 2 = probe Pb2; 3 = probe Pb3
0/1/2/3 1 1 1 1 num
HACCP (“HCP” folder)
SHH Maximum HACCP alarm signals threshold -55,0...150
0 0 0 0
°C/°F
SLH Minimum HACCP alarm signals threshold -55,0...150 0 0 0 0 °C/°F
drA
Minimum time spent in critical range for the event to be recorded. After this a HACCP
alarm will be triggered and logged
0 ... 99 0 0 0 0 min
drH HACCP alarm reset time after last reset 0 ... 250 0 0 0 0 hours
H50
Enable HACCP and alarm relay functions.
0= HACCP alarms NOT enabled;
1 = HACCP alarms enabled and alarm relay NOT enabled;
2 = HACCP alarms enabled and alarm relay enabled
0/1/2 0 0 0 0 num
H51 HACCP alarm exclusion time 0 ... 250 0 0 0 0 min
CONFIGURATION (“CnF” folder)
H00 Probe type selection.
0 = PTC; 1 = NTC; 2 = PT1000 0/1/2
1 1 1 1
num
H11
Configuration of digital input 1/polarity.
0 = disabled; ±1 = defrost; ±2 = economy Setpoint; ±3= AUX;
±4= door switch; ±5 = external alarm; ±6= Standby; ±7= pressure switch; ±8=
Deep Cooling; ±9= disable HACCP alarm logging.
NOTE: • the “+” sign indicates that the input is active if the contact is closed.
• the “-” sign indicates that the input is active if the contact is open.
-9 ... +9 2 2 4 2 num
H12 Configuration of digital input 2/polarity. Same as H11 -9 ... +9 0 0 0 0 num