Manual R1140-X0-ST-EN Release: 1.06 © Elotech GmbH Page 8/24
6.1 Configuration Level
(Press „P“ and „E“-key appr. 3sec.)
Display Parameter Adjustment range
„Process" DisplaySet“
Cont Controller on/off OFF Control action off (stand-by operation)
on Control action on (ex works)
Stand-by operation:
All control outputs are switched „off“. The alarm-relays are not
energized. All parameters can be preselected and preadjusted.
ConF Controller 2P h 2-point-controller „heating“ (ex works)
configuration 2P c 2-point-controller „cooling“
2Pnc 2-point-controller, non-linear-cooling*)
3P 3-point controller:"heating - off - cooling"
3Pnc 3-point controller:"heating - off - cooling
", non-linear cooling*)
*) Cooling action can be pre-selected with either linear or
non-linear-cooling response curve (e.g. for vapour cooling).
Out4 Configuration Output 4 OFF OUT4 not active
Only valid for types R1140-10:
- Controller output,
instead of OUT1: bi 1 Logic output / bistable voltage signal 0/18VDC
- 3-point-controller output
„cooling“, instead of OUT2: bi 2 Logic output / bistable voltage signal 0/18VDC
Only valid for types R1140-60/61: Type 60 Type 61
- Controller output,
instead of OUT1: C1. 0 control output 0...20mA 0…10V
C1. 4 control output 4...20mA 2…10V
- 3-point-controller output
„cooling“, instead of OUT2: C2. 0 control output 0...20mA 0…10V
C2. 4 control output 4...20mA 2…10V
Only valid for types R1140-60/61-00-2/4/5-x
- Process value output Pr. 0 process value output 0...20mA 0…10V
Pr. 4 process value output 4...20mA 2…10V