ems100 Product Manual, Issue 4
www.nexo.com
Page 39
If in Saving mode and set point is achieved within twenty (20) cycles
the controller reverts to normal operation and alternately displays:
d0/3Bars.
An audio alarm sounds for ten (10) seconds, every ten (10) minutes.
/
If set point is not achieved within twenty (20) cycles the compressor
switches o and the controller displays 3BarStack: An audio alarm
sounds continuously.
Door open alarms are triggered if the cooler door is left open for longer than the time dened by the alarm
delay (Ad) parameter.
If the door is closed, and a door open alarm is registered, this may indicate problems with the cooler door
or the door switch.
Follow the chart to troubleshoot door open alarms on coolers with a door switch.
Ensurecooler
doorclosed
No No No
SeeAlarmsforfurther
information
Applyhandheldactivator
(magnet)against
thedoorswitch
Ensureareainfrontof
motionsensor isclear
Performahalfreset
Yes
Yes
Controller
operating
correctly
Yes
No
Replace
controller
Yes
Activatormisaligned
Realignactivator
Doorswitch
connectionOK?
Replace
door
switch
RemakeconnectionNo No
Yes
Yes