Quick Start Guide Minipack PS System 356808.103, 1v2-2008-10
20
Battery Interface Card ~ Terminals & Pin-out
The Smartpack controller’s battery monitoring signals are accessible on D-Sub connectors CON4
and CON3, on the controller’s rear panel.
Using the Battery Connection Kit which consists of a Battery Interface Card (Art. 200576) and
a standard 15 pins D-Sub cable you can make the signals on CON4 accessible at any suitable
location inside your system, e.g. near the battery blocks.
When extra battery monitoring signals are required, you can use an extra Battery Connection Kit
connected to the controller’s CON3.
For detailed information about the card’s pin-out location and terminal block connections, see the
figures in this section.
For temperature monitoring of the battery
compartment, we recommend the use of the
Temperature Sense Kit, instead of
connecting the sensor cable directly to the
terminals, pin 9-10.
The Temperature Sense Kit is connected to
the Battery Interface Card (Art. 200576), or
directly to the controller’s CON3 or CON4,
if unused.
15 pins D-Sub cable
Card Art.200576
Battery Connection Kit
Temp. senso
r
Temp. Sensor cable
Temperature Sense Kit
In
1.
5
mm
2
, max.
wire section
Battery Connections (Internal)
Configurable monitoring digital inputs
FUNCTION SIGNAL PIN-OUT
(
Internal Connections
)
4
3
2
1
5
9
8
7
6
10
14
13
12
11
X4
Batt. Symmetry 1
+
+
+
+
Batt. Symmetry 2
Batt. Symmetry 3
Batt. Symmetry 4
(From internal
batteries)
(From area with
internal batteries)
Temperatu
r
e
senso
r
+
Temperature Sense 1
(NA)
(NA)
(From area with
internal batteries)
Temperatu
r
e
senso
r
15-pins
D-Sub female
(Alternative use of Temp. Sense Kit,
instead of connecting to X4: 9-10)
Temperature Sense 1
X**/X*
15-pins D-Sub male
1
5
11 15
Card Art.200576
To Smartpack,
CON4
CON3A o
r
CON4A
15-pins
D-Sub female
111
515
In
1.
5
mm
2
, max.
wire section
Battery Connections (Internal)
Configurable monitoring digital inputs
FUNCTION SIGNAL PIN-OUT
(
Internal Connections
)
4
3
2
1
5
9
8
7
6
10
14
13
12
11
X3
+
+
+
+
(From internal
batteries)
(From area with
internal batteries)
Temperatu
r
e
senso
r
+
(From area with
internal batteries)
Temperatu
r
e
senso
r
15-pins
D-Sub female
(Alternative use of Temp. Sense Kit,
instead of connecting to X3: 9-10)
Temperature Sense 2
X**/X*
15-pins D-Sub male
1
5
11 15
Card Art.200576
To Smartpack,
CON3
CON3A o
r
CON4A
15-pins
D-Sub female
111
515
The Temperature Sense Kits may also be connected directly to the
Smartpack controller’s CON3 or CON4, if these connectors are unused.
Batt. Symmetry 5
Batt. Symmetry 6
Batt. Symmetry 7
Batt. Symmetry 8
Temperature Sense 2
Batt Current 2
Batt Fuse Fail 2
Battery Interface Card, Art. 200576
14
1
Serial Switch
For Temp. Sense Ki
t
CON3A or CON4A
X3/X4
X**/X*
1
Terminals & Pin-out Location
CON3
CON2
CON4
CON5
CON1
PCB 200576
PCB 200576
Smartpack
Appendix Battery Monitoring
Batt. Symmetry Kit, Art. 200830
Cable
Lugs
Single Wire

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eltek Valere Minipack and is the answer not in the manual?

Eltek Valere Minipack Specifications

General IconGeneral
BrandEltek Valere
ModelMinipack
CategoryPower Supply
LanguageEnglish

Related product manuals