Standards
FM Class 3600 - 2011, FM Class 3611 - 2004, FM Class 3616 -
2011, UL 50 - 11
th
Ed, ANSI/ISA 61010-1 - 2012
Markings
NI CL 1, DIV 2, GP A, B, C, D T4; Suitable for use in CL II, III, DIV
2, GP F, G T4; T4(-40 °C ≤ T
a
≤ +60 °C); Nonincendive outputs
to remote antenna when connected per Rosemount drawing
01420-1011; Type 4X
Special Conditions for Safe Use(X):
1. Explosion Hazard. Do not disconnect equipment when a flammable
or combustible atmosphere is present.
9.7 Canada
N6 Canada Division 2
Certificate
CSA 70010780
Standards
CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA Std C22.2 No.
94-M91 (R2001), CSA Std C22.2 No. 142-M1987, CSA Std
C22.2 No. 213-M1987, CSA C22.2 No. 61010-1 – 2012
Markings
Suitable for Class 1, Division 2, Groups A, B, C, and D, T4; when
connected per Rosemount drawing 01420-1011; Type 4X
Special Conditions for Safe Use(X)
1. Explosion Hazard. Do not disconnect equipment when a flammable
or combustible atmosphere is present.
9.8
Europe
N1 ATEX Type n
Certificate
Baseefa07ATEX0056X
Standards
EN 60079-0: 2012, EN 60079-15: 2010
Markings
II 3 G Ex nA IIC T4 Gc, T4(-40 °C ≤ T
a
≤ +65 °C), V
MAX
= 28
Vdc
Special Conditions for Safe Use(X)
1. The equipment is not capable of withstanding the 500V insulation
test required by clause 6.5.1 of EN 60079-15:2010. This must be
taken into account when installing the equipment.
2. The surface resistivity of the antenna is greater than 1GΩ. To avoid
electrostatic charge build-up, it must not be rubbed with a dry cloth
or cleaned with solvents.
ND ATEX Dust
September 2020 Quick Start Guide
Quick Start Guide 27