28 Installation
UM5C05C P0745680 Standard 6.00 October 2001 Emerson Energy Systems
3.7. Connecting the control signals
For all applications with conventional controllers ( such as NT6C25BA or
NT6C25BB ) or front access controllers ( NT6C25FA ), execute the steps
contained in Procedure 7 to connect the NT5C05CC rectifier ( see Figure
9 ).
Procedure 7 - Connecting the NT5C05CC to the controller
Step Action
1
Connect each rectifier to the NT6C43PB board ( positions J1 to J6 ),
located at the top front of the cabinet or frame, with P0747000
cables.
2
Connect the NT6C43PB board ( positions J7 to J12 ) to the
controller with P0736355 cables for conventional controllers ;
and with P0736268 cables for front access controllers.
end
Figure 9 - Typical connections between rectifiers and the conventional
controller
Rectifier
#6
J13
J1 J2 J3 J4 J5 J6
J7 J8 J9 J10 J11 J12
MONITOR
NT6C43PB
Cables P0736355
CONTROLLER NT
(NT6C25BA or NT6C25BB)
Cables P0747000
Rectifier
#5
Rectifier
#4
Rectifier
#3
Rectifier
#2
Rectifier
#1