Emerson Energy Systems Rectifier 200I/48NT5C05C Installation and User Manual
5. Operation
5.1. Standard settings
The parameters of the NT5C05CA / CB / CC rectifiers are set as indicated
in Table 15. For different settings refer to User Manual Voltage_level
entitled Voltage Level Limits for Power Plants, Rectifiers and Controllers.
Table 15 - Standard settings for the rectifier
Parameter Setting
Rectifier float output voltage ( FLOAT ) 52.1 ±0.1 V dc
Rectifier equalize output voltage
( EQUALIZE )
52.8 ±0.1 V dc
Rectifier high voltage shutdown threshold 56.5 ±0.1 V dc
Rectifier output current limit 205 A ±5 A
Rectifier start delay 4 sec
Low ac input disconnect 330 ±5 V ac
Low ac input reconnect 350 ±5 V ac
High ac input disconnect 475 ±5 V ac
High ac input reconnect 460 ±5 V ac
Load sharing method Slope