iTrust Adapt UPS 20
k
V
A
User
Ma
nu
a
l
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Copyright © 2010 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
Emerson Network Power Co., Ltd.
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
E-mail: support@emersonnetwork.com.cn

Table of Contents

Questions and Answers

  • R
    Richard RhodesAug 20, 2025
    What to do if the Emerson Adapt displays 'BATTERY LOW TO BE SHUTDOWN'?
    • J
      johndavenportAug 20, 2025
      If the yellow indicator illuminates, and the buzzer beeps for a long time in Battery mode, and the LCD displays BATTERY LOW TO BE SHUTDOWN, it signifies that the battery voltage is low and the Emerson UPS is about to shut down. To prevent data loss or damage, immediately save your work and turn off the load. Alternatively, connect backup AC power to the UPS input.
  • K
    Karen VangAug 22, 2025
    What to do if my Emerson UPS displays 'OVERLOAD'?
    • E
      Eric CooperAug 22, 2025
      If the buzzer beeps every 0.5 second, and the LCD displays OVERLOAD on your Emerson UPS, it means there is an overload. The rectifier is overloaded, or the mains voltage is too high. You need to remove non-priority load.
  • Z
    zheathAug 25, 2025
    What to do if my Emerson Adapt UPS displays 'BATTERY FAL'?
    • L
      Laura MannAug 25, 2025
      If the FAULT indicator illuminates, the LCD displays BATTERY FAL, and the BATTERY indicator flashes on your Emerson UPS, several issues could be the cause. First, check if the external battery breaker is open and close it. Then, check that the external battery cables are properly connected and not reverse-connected. If the problem persists, the battery may be damaged, and you should contact the local service center of Emerson to replace it.
  • B
    Bryan FarrellAug 27, 2025
    What to do if my Emerson Adapt displays 'TEMP OVER'?
    • R
      ryan42Aug 27, 2025
      If your Emerson UPS is beeping for a long time, the FAULT indicator is illuminated, and the LCD displays TEMP OVER, it indicates an internal over-temperature issue or a fan fault. Here's what you should do: 1. Check that the fan is unobstructed and air blows out from the air outlet on the rear panel. 2. Ensure clearances on both sides and at the back of the UPS are greater than 200mm. 3. Verify that the ventilation holes on the front panel, side panels, base plate, and rear panel of the UPS are unobstructed. After checking these, wait for ten minutes and then restart the UPS.
  • B
    Barry LesterAug 28, 2025
    What to do if my Emerson Adapt UPS displays 'OUTPUT SHORT'?
    • J
      John JensenAug 28, 2025
      If the buzzer beeps for a long time, the FAULT indicator illuminates, and the LCD displays OUTPUT SHORT on your Emerson UPS, it means there is a short circuit. Remove the output short circuit fault and restart the UPS.
  • Z
    Zachary ConnerAug 30, 2025
    Why is my Emerson Adapt in battery mode when the mains supply is normal?
    • A
      Andrea LewisAug 30, 2025
      If the mains supply is normal, but the UTILTITY indicator is off, and the Emerson UPS is in Battery mode, it could be due to two reasons. Either the UPS mains switch is open, in which case you should close it. Or the input cables are improperly connected, so you should connect the UPS input cables properly.
  • D
    Donna TaylorSep 1, 2025
    Why Emerson Adapt UPS has no display and doesn't self-test?
    • A
      Amy GarciaSep 1, 2025
      If the mains switch is closed, but the Emerson UPS provides no display on the operation and display panel, and the UPS does not conduct self-test, it may be due to the main supply not being connected to the UPS. Check that the UPS input cables are connected properly. Alternatively, the input voltage may be too low. Use a voltmeter to confirm that the UPS input voltage is within specifications.
  • J
    Jordan DixonSep 3, 2025
    Why does my Emerson Adapt UPS have reduced battery time?
    • J
      John SmithSep 3, 2025
      If your Emerson UPS has reduced battery time, it might be because the battery is not fully charged. When the mains power is normal, charge the battery for more than 8 hours, and then test the battery discharge time. Another reason could be that the battery is old and not able to hold a full charge. In this case, contact the local service center of Emerson to replace the battery.
  • J
    Jaclyn MackSep 5, 2025
    What to do if no output voltage from Emerson UPS?
    • M
      Michael SullivanSep 5, 2025
      If there is no UPS alarm, but no UPS output voltage from your Emerson UPS, the output cables might be improperly connected. Make sure the output cables are properly connected.
  • F
    feliciadavisSep 7, 2025
    Why is the UTILITY indicator flashing on my Emerson Adapt?
    • E
      Elizabeth HudsonSep 7, 2025
      If the UTILITY indicator flashes on your Emerson UPS, it means the mains voltage output or frequency is outside specifications. If the UPS is operating in Battery mode, pay attention to the battery backup time.

Summary

Safety Precautions

High Leakage Current Warning

Warns about high leakage current and the need for proper earth connection and RCCB selection.

Reflected Protection Signal

Explains the zero-voltage contact closure signal for protection against backfeeding voltage.

Battery Safety Precautions

High Voltage Battery Warning

Warns that battery terminal voltage can exceed 400Vdc, requiring trained personnel and proper tools.

Product Introduction

Key Features

Lists the main capabilities and benefits of the iTrust Adapt UPS, such as dual output modes and parallel connection.

UPS Operating Principle and States

Technical Specifications

Electrical and Performance Specs

Provides detailed electrical and performance specifications for the UPS.

Environmental and Physical Specs

Details environmental conditions, size, and weight specifications for the UPS.

Installation Guide

Mechanical Installation

External Protective Devices

Input Protection Requirements

Explains overcurrent protection for input and the use of RCCBs for earth leakage.

Battery and Output Protection

Details overcurrent protection for battery input and UPS output distribution.

Power Cable Connections

Parallel System Setup

Double Bus System Configuration

Operation and Display Panel

LCD Screen Navigation and Menus

Explains the different LCD screens and how to navigate through the menu system.

System Messages and Alarms

Covers prompt windows, alarm messages, and troubleshooting guidance.

UPS Operation Procedures

Starting and Shutting Down the UPS

Step-by-step guides for starting, shutting down, and emergency power off procedures.

UPS Maintenance

Battery Care and Testing

Details battery maintenance, health management, and function checks.