Installation and Maintenance
Part Number: E2K-402-0313, Rev. A
Mar 2013
17
Section 6: Futronic II 83957
Futronic II 83957
TIP:
To measure BAND, place Voltmeter (-) Probe in Green (SIG) test point and (+) probe in
Red (FB) test point. Move valve using Handwheel. Observe reading when valve repositions
(BAND adjustment is ±1% to 7%.).
* 83957-2 has a thirty (30) second delay for 100 starts per hour maximum.
NOTE:
Feedback Pot may be mounted on MDPI (Multi-turn valves) or mounted on gear cover
(1/4 Turn valves).